SANS 10400 Statutory Compliance Notice
All architectural plans submitted to South African local authorities must comply with Act 103 of 1977 and municipal bylaws.
Across South Africa's metropolitan municipalities—including the City of Johannesburg, City of Cape Town, City of Tshwane, and eThekwini—a remarkable percentage of first-time building plan submissions are referred back by Building Control Officers (BCOs) not because the architectural design violates zoning, but because the drawing sheets lack explicit, legally enforceable specification notes. When searching for SANS 10400 standard notes building plans AutoCAD Revit South Africa, registered professionals need more than generic disclaimers; they need audit-ready technical wording that demonstrates unambiguous compliance with the National Building Regulations and Building Standards Act (Act 103 of 1977) and the deemed-to-satisfy provisions of SANS 10400.
As Plan Comply's Pre-Submission Audit Engineering Team, we review municipal submission sets daily across AutoCAD, Autodesk Revit, and Graphisoft ArchiCAD workflows. A BCO cannot infer structural intent, damp-proofing continuity, safety glazing classifications, or energy compliance solely from 2D linework or 3D BIM geometry. Under the regulatory framework administered by local authorities, the drawings and their accompanying specification notes form a binding legal contract between the property owner, the SACAP-registered professional, the appointed competent persons, and the municipality.
Why Municipal Plan Examiners Reject Generic Specification Notes
Legacy CAD templates circulating in South African drawing offices frequently cite superseded SABS 0400 clauses, omit SANS 10400-XA energy parameters entirely, or leave blank placeholders for structural engineer appointments. In electronic submission portals—such as Cape Town's Development Management Scheme (DMS) e-Services portal or Johannesburg's digital plan scrutiny workflow—examiners apply rigid statutory checklists. If a sheet shows a retaining wall, a low-level window, or a flat roof without the corresponding SANS 10400 Part D, Part N, or Part XA declaration, the application triggers an immediate Request for Additional Information (RAI) or formal refusal.
For municipality-specific portal formatting rules, review our dedicated guides on the City of Johannesburg building plan submission workflow and the City of Cape Town DMS & SANS 10400 submission checklist.
Municipal Title-Block Declarations & SACAP Form 1 / Form 2 Notes (SANS 10400-A)
Before detailing individual construction elements, your primary Layout or Title Sheet must anchor the legal authority of the submission under SANS 10400-A (Application of the National Building Regulations). Municipal scrutineers immediately verify property identification, occupancy classification (Regulation A20), zoning parameters, SACAP registration validity, and whether rational designs or structural elements trigger SANS 10400-A Form 1 and Form 2 appointments.
Copy-Paste AutoCAD / Revit Block: Title-Block & SACAP Competency Declaration
GENERAL STATUTORY & SANS 10400-A DECLARATIONS:
1. ALL BUILDING WORK SHALL COMPLY STRICTLY WITH THE NATIONAL BUILDING REGULATIONS AND BUILDING STANDARDS ACT (ACT 103 OF 1977), SANS 10400 PARTS A TO XA (LATEST APPLICABLE EDITIONS), AND ALL RELEVANT MUNICIPAL BYLAWS.
2. OCCUPANCY CLASSIFICATION (REG. A20): [INSERT e.g. H4 DWELLING HOUSE / H3 DOMESTIC RESIDENCE / G1 OFFICES].
3. SITE & ZONING DATA: ERF [NUMBER], TOWNSHIP [NAME], ZONING [e.g. RESIDENTIAL 1]. PERMISSIBLE COVERAGE: [X]% | PROPOSED COVERAGE: [X]%. PERMISSIBLE FAR/BULK: [X] | PROPOSED: [X]. BUILDING LINES: STREET [X]m, LATERAL [X]m, REAR [X]m.
4. DIMENSION HIERARCHY: FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED MEASUREMENTS. DO NOT SCALE FROM DRAWINGS. ALL LEVELS AND BOUNDARY PEGS TO BE VERIFIED ON SITE BY CONTRACTOR PRIOR TO COMMENCING WORK.
5. SACAP & COMPETENT PERSON DECLARATION: THE ARCHITECTURAL WORK IS SUBMITTED BY [FULL NAME], SACAP REG. NO. [e.g. PAT/XXXX OR PR.ARCH XXXX]. WHERE STRUCTURAL ELEMENTS FALL OUTSIDE DEEMED-TO-SATISFY RULES (INCLUDING SUSPENDED SLABS, CANTILEVERS, RETAINING WALLS >1.2m, ENGINEERED ROOF TRUSSES, OR PART XA RATIONAL DESIGN), APPOINTMENTS SHALL BE LODGED VIA SANS 10400-A FORM 1 & FORM 2 BY AN ECSA-REGISTERED COMPETENT PERSON PRIOR TO CONSTRUCTION / OCCUPATION.Drafting Tip: Never submit a plan showing prefabricated timber roof trusses, precast concrete slabs, or steel portal frames without explicitly referencing the Form 2 Competent Person requirement in your general notes—even where the municipality permits deferred structural submission prior to roof inspection.
Copy-Paste SANS 10400 Standard Notes by Part (AutoCAD, Revit & ArchiCAD)
The following modular blocks are structured so you can paste them directly into an AutoCAD MTEXT object, a Revit Legend View (or Sheet Drafting View), or an ArchiCAD Master Layout Worksheet. Replace bracketed variables [...] with project-specific values before exporting to PDF.
1. SANS 10400-A & Part C: Administration, Dimensions & Room Heights
SANS 10400-A & PART C (DIMENSIONS & CLEARANCES):
- MINIMUM CLEAR CEILING HEIGHTS TO COMPLY WITH SANS 10400-C: HABITABLE ROOMS (BEDROOMS, LIVING, DINING, KITCHENS) MIN. 2400mm FROM FINISHED FLOOR LEVEL (FFL) TO UNDERSIDE OF CEILING (2100mm FOR PASSAGES, BATHROOMS, WCs, AND GARAGES). UNDER SLOPING CEILINGS, MIN. 2400mm OVER AT LEAST 50% OF FLOOR AREA WITH NO PORTION BELOW 2100mm WHERE COUNTED AS HABITABLE SPACE.
- MINIMUM FLOOR AREAS & PLAN DIMENSIONS OF HABITABLE ROOMS TO COMPLY WITH SANS 10400-C (MIN. 6.0 m² WITH LEAST HORIZONTAL DIMENSION NOT LESS THAN 2.0m, EXCLUDING KITCHEN/SCULLERY).
- CONTRACTOR TO VERIFY ALL EXISTING SERVICES, INVERT LEVELS, AND BOUNDARY BEACONS PRIOR TO EXCAVATION. ANY DISCREPANCY TO BE REPORTED TO THE PRINCIPAL AGENT IMMEDIATELY.2. SANS 10400-D: Public Safety, Balustrades & Swimming Pools
Missing balustrade and pool safety notes are among the top five causes of conditional holds in Cape Town and eThekwini, particularly on multi-storey dwellings and sloping sites.
SANS 10400-D (PUBLIC SAFETY, BALUSTRADES & POOL ENCLOSURES):
- BALUSTRADES / GUARDRAILS: ALL CHANGES IN LEVEL EXCEEDING 1000mm (INCLUDING BALCONIES, STAIRCASES, LANDINGS, AND RETAINING WALLS) TO BE PROTECTED BY A RIGID BALUSTRADE MIN. 1000mm HIGH ABOVE FFL / PITCH LINE.
- OPENINGS IN BALUSTRADES SHALL NOT PERMIT THE PASSAGE OF A 100mm DIAMETER SPHERE. NO HORIZONTAL RAILS OR FOOTHOLDS THAT FACILITATE CLIMBING BY CHILDREN ARE PERMITTED WHERE APPLICABLE UNDER SANS 10400-D.
- SWIMMING POOL ENCLOSURE (WHERE APPLICABLE): POOL AREA TO BE COMPLETELY ENCLOSED BY A FENCE OR WALL MIN. 1200mm HIGH MEASURED FROM OUTSIDE GROUND LEVEL, WITH NO VERTICAL OR HORIZONTAL APERTURES EXCEEDING 100mm. ACCESS GATE TO BE SELF-CLOSING AND FITTED WITH A SELF-LATCHING DEVICE MOUNTED AT LEAST 1500mm ABOVE GROUND LEVEL OR ON THE POOL SIDE, OPENING OUTWARDS AWAY FROM THE POOL.3. SANS 10400-K: Walls, Damp Proofing (DPC), Lintels & Foundations
Council inspectors scrutinize section drawings for continuous damp-proof courses (DPC), cavity weeping, and masonry reinforcement. Pair these text specifications with clear graphical DPC lines on your 1:20 or 1:50 wall sections.
SANS 10400-K & PART H (FOUNDATIONS, MASONRY WALLS, DPC & LINTELS):
- FOUNDATIONS: STRIP FOOTINGS TO BE FOUNDED ON FIRM NATURAL SUBSOIL AT MIN. [600mm] DEPTH BELOW NGL (OR AS DIRECTED BY STRUCTURAL ENGINEER / GEOTECHNICAL REPORT). CONCRETE STRENGTH MIN. 15MPa/19mm (OR 20MPa/25MPa PER ENGINEER DETAIL). UNDER-SLAB DPM: 250 MICRON POLYETHYLENE SHEETING (SANS 952 TYPE C) LAPPED 150mm AND TAPED OVER 50mm CLEAN SAND BEDDING ON COMPACTED HARDCORE FILL.
- MASONRY WALLS: ALL EXTERNAL WALLS TO BE [220mm SOLID / 270mm CAVITY] CLAY BRICKWORK (SANS 227) IN CLASS II MORTAR (1:1:6 CEMENT:LIME:SAND OR EQUIVALENT). CAVITY WALLS TO HAVE STAINLESS STEEL OR GALVANISED BUTTERFLY WALL TIES AT MAX. 450mm VERTICALLY x 900mm HORIZONTALLY (STAGGERED), WITH WEEP HOLES AT MAX. 1000mm CENTRES ABOVE FLASHING.
- DAMP-PROOF COURSE (DPC): PROVIDE 375 MICRON EMBOSSED POLYETHYLENE DPC (SANS 952 TYPE B) UNDER ALL WALLS AT MIN. 150mm ABOVE FINISHED GROUND LEVEL (FGL) / PAVING, STEPPED ON SLOPING SITES. PROVIDE VERTICAL DPC AT ALL RETAINING PORTIONS, WINDOW REVEALS, AND CAVITY CLOSURES.
- LINTELS & BRICKFORCE: PROVIDE PRECAST PRESTRESSED CONCRETE LINTELS (OR IN-SITU REINFORCED CONCRETE BEAMS PER ENGINEER) OVER ALL OPENINGS UP TO [3000mm], WITH MIN. 150mm BEARING EACH SIDE (MIN. 225mm FOR SPANS >1500mm) AND MIN. 3 COURSES BRICKFORCE IN EVERY COURSE ABOVE LINTELS FOR AT LEAST 4 COURSES. PROVIDE BRICKFORCE EVERY 4TH COURSE IN STANDARD WALLING AND CONTINUOUSLY ABOVE ALL DOOR/WINDOW HEADS.4. SANS 10400-M: Stairways, Ramps & Handrails
SANS 10400-M (STAIRWAYS, RAMPS & HANDRAILS):
- STAIRWAY GEOMETRY: MAX. RISER HEIGHT = 200mm (CONSISTENT THROUGHOUT FLIGHT); MIN. GOING (TREAD) = 250mm; COMFORT FORMULA 550mm <= (2R + G) <= 700mm. MIN. CLEAR STAIR WIDTH = [900mm DOMESTIC / 1100mm PUBLIC]. MIN. HEADROOM CLEARANCE = 2100mm MEASURED VERTICALLY FROM PITCH LINE.
- LANDINGS: PROVIDE LEVEL LANDINGS AT TOP AND BOTTOM OF EVERY FLIGHT WITH LENGTH NOT LESS THAN STAIR WIDTH. NO DOOR SWING TO ENCROACH ON STAIR LANDINGS UNLESS CLEARANCES COMPLY WITH SANS 10400-M.
- HANDRAILS: PROVIDE CONTINUOUS HANDRAIL ON AT LEAST ONE SIDE (BOTH SIDES WHERE WIDTH EXCEEDS 1100mm) AT HEIGHT 850mm TO 1000mm MEASURED VERTICALLY FROM NOSING LINE. ALL TREADS TO HAVE SLIP-RESISTANT NOSINGS.5. SANS 10400-N: Safety Glazing & Window Schedule Notes
Every window and door schedule submitted for municipal approval must explicitly identify where safety glass is required under SANS 10400-N and SANS 1263-1. Simply labelling a window "W01" without thickness or safety glass designation is a guaranteed rejection trigger in Johannesburg and Tshwane.
SANS 10400-N (GLAZING & SAFETY GLASS SCHEDULE NOTES):
- ALL GLAZING THICKNESSES, PANE SIZES, AND WIND-LOAD CLASSIFICATIONS TO COMPLY WITH SANS 10400-N TABLES AND SANS 1263 PART 1.
- SAFETY GLAZING (TOUGHENED OR LAMINATED SAFETY GLASS MARKED PERMANENTLY WITH SANS 1263-1 COMPLIANCE STAMP) SHALL BE INSTALLED IN ALL CRITICAL LOCATIONS:
(a) ALL GLAZED DOORS AND GLAZED SIDE PANELS WITHIN 300mm OF ANY DOOR EDGE UP TO 2000mm ABOVE FFL;
(b) LOW-LEVEL GLAZING WHERE THE SILL / BOTTOM EDGE IS LESS THAN 500mm ABOVE FFL;
(c) ALL BATH AND SHOWER ENCLOSURES / SCREENS AND WINDOWS ADJACENT TO BATHS/SHOWERS UP TO 1800mm ABOVE BASE LEVEL;
(d) SHOPFRONTS, BALUSTRADE INFILL PANELS, AND OVERHEAD/SLOPED GLAZING (LAMINATED SAFETY GLASS ONLY FOR OVERHEAD GLAZING).
- ALL ALUMINIUM / TIMBER / uPVC FRAMES TO BE SEALED WATERTIGHT AGAINST REVEALS WITH NEUTRAL-CURE SILICONE AND FITTED WITH APPROVED SUB-SILL FLASHINGS.6. SANS 10400-O: Natural Lighting & Ventilation Schedule Notes
Municipal examiners cross-check floor areas against openable window areas. Adding a structured Natural Light & Ventilation note (paired with an automated Revit schedule or AutoCAD table) removes ambiguity during scrutiny.
SANS 10400-O (LIGHTING & VENTILATION):
- NATURAL LIGHTING: ALL HABITABLE ROOMS PROVIDED WITH GLAZED OPENINGS HAVING AN AGGREGATE UNOBSTRUCTED GLASS AREA OF NOT LESS THAN 10% OF THE ROOM FLOOR AREA (OR MIN. 0.2 m², WHICHEVER IS GREATER).
- NATURAL VENTILATION: ALL HABITABLE ROOMS, BATHROOMS, AND WCs PROVIDED WITH OPENABLE WINDOW/DOOR SECTIONS EQUAL TO AT LEAST 5% OF THE FLOOR AREA (OR MIN. 0.2 m², WHICHEVER IS GREATER). NO HABITABLE ROOM VENTILATES SOLELY INTO AN ENCLOSED GARAGE OR UNVENTILATED VERANDA.
- MECHANICAL VENTILATION (INTERNAL WCs / BATHROOMS / KITCHENS WITHOUT EXTERNAL WINDOWS): INSTALL CONTINUOUS OR LIGHT-SWITCH-ACTIVATED MECHANICAL EXTRACTION DUCTED DIRECTLY TO OUTSIDE AIR (NOT INTO ROOF VOID), DESIGNED TO ACHIEVE MIN. EXTRACTION RATES PER SANS 10400-O (e.g. MIN. 10 L/s PER WC PAN / 25 L/s PER BATHROOM OR RATIONAL DESIGN BY MECHANICAL ENGINEER).7. SANS 10400-P: Drainage, Plumbing & Stormwater Separation
Drainage layouts must be backed by airtight technical specifications—particularly regarding pipe gradients, venting, rodding access, and the strict legal prohibition against discharging stormwater into municipal foul sewers.
SANS 10400-P (FOUL DRAINAGE, PLUMBING & STORMWATER):
- PIPEWORK & GRADIENTS: ALL UNDERGROUND FOUL DRAINAGE TO BE 110mm uPVC CLASS 34 HEAVY DUTY (SANS 791) LAID IN STRAIGHT LINES ON COMPACTED SAND BEDDING AT A UNIFORM FALL OF 1:40 TO 1:60 (MIN. 1:60 FOR 110mm SEWER). WATER SUPPLY PIPEWORK TO COMPLY WITH SANS 10252-1 AND SANS 10254 (HOT WATER CYLINDERS WITH DRIP TRAYS & VACUUM BREAKERS).
- ACCESS & CLEANING: PROVIDE INSPECTION EYES (IE) AT ALL BENDS AND JUNCTIONS, AND RODDING EYES (RE) BROUGHT UP TO GROUND LEVEL AT HEAD OF ALL DRAINS AND AT MAX. 24m INTERVALS ON STRAIGHT RUNS.
- GULLIES & TRAPS: EVERY WASTE PIPE TO DISCHARGE OVER A TRAPPED GULLY WITH DISH/RIM FINISHED MIN. 150mm ABOVE SURROUNDING PAVING OR GROUND LEVEL TO PREVENT STORMWATER INGRESS.
- VENTILATION: PROVIDE 110mm SOIL VENT PIPE (SVP) / TWO-WAY VENT VALVE TERMINATING MIN. 900mm ABOVE ANY OPENABLE WINDOW OR DOOR WITHIN 2.5m HORIZONTALLY, AND MIN. 150mm ABOVE ROOF EAVES.
- STORMWATER SEPARATION: STRICTLY NO STORMWATER FROM ROOFS, PAVING, OR COURTYARDS MAY ENTER THE MUNICIPAL FOUL SEWER. ALL STORMWATER TO BE DISCHARGED VIA SURFACE CHANNELS / SUBSOIL PIPES TO STREET KERB OR APPROVED ON-SITE RETENTION/SOAKAWAY PER MUNICIPAL STORMWATER BYLAW.8. SANS 10400-T: Fire Protection & Boundary Fire Walls
SANS 10400-T (FIRE PROTECTION):
- LATERAL & REAR BOUNDARY SAFETY DISTANCES: WHERE ANY EXTERNAL WALL IS LOCATED LESS THAN 1000mm FROM A LATERAL OR REAR BOUNDARY (OR AS REQUIRED BY OCCUPANCY & TABLE 2 OF SANS 10400-T), SUCH WALL SHALL HAVE ZERO UNPROTECTED OPENINGS AND ACHIEVE MIN. [30 / 60] MINUTES FIRE RESISTANCE, EXTENDED TO UNDERSIDE OF NON-COMBUSTIBLE ROOF COVERING WITH NON-COMBUSTIBLE UNDER-ROOF FIRE STOPPING / PARAPET WALL AS REQUIRED.
- GARAGES ATTACHED TO DWELLINGS: WALLS AND DOORS SEPARATING AN ATTACHED GARAGE FROM HABITABLE ROOMS SHALL ACHIEVE MIN. 30 MINUTES FIRE RESISTANCE; CONNECTING DOOR TO BE SOLID-CORE FLUSH TIMBER (MIN. 40mm THICK) OR FIRE-RATED DOOR FITTED WITH SELF-CLOSING DEVICE AND NO VENTILATION GRILLE.
- INTERCONNECTED SMOKE DETECTION & PORTABLE FIRE EXTINGUISHERS TO BE INSTALLED WHERE REQUIRED BY OCCUPANCY CLASS AND MUNICIPAL FIRE BYLAWS.9. SANS 10400-XA: Energy Usage in Buildings & Fenestration
Energy efficiency scrutiny has intensified significantly following the rollout of updated SANS 10400-XA provisions (including the revised climatic zoning and fenestration rules under SANS 10400-XA:2021). Failing to specify your Climatic Zone, roof R-value, hot water heating compliance, and glazing ratio is one of the fastest ways to trigger an audit hold. For a complete deep dive on fenestration math, consult our SANS 10400-XA energy efficiency & fenestration guide.
SANS 10400-XA (ENERGY USAGE IN BUILDINGS):
- APPLICABLE STANDARD & CLIMATIC ZONE: BUILDING DESIGNED TO COMPLY WITH SANS 10400-XA ([SPECIFY EDITION, e.g. 2021] - CLIMATIC ZONE [1-7, e.g. ZONE 1 JOHANNESBURG / ZONE 4 CAPE TOWN / ZONE 5 DURBAN]).
- HOT WATER HEATING: AT LEAST 50% OF ANNUAL DOMESTIC HOT WATER HEATING ENERGY DEMAND TO BE SUPPLIED BY MEANS OTHER THAN ELECTRICAL RESISTANCE HEATING (E.G. [SOLAR WATER HEATER / HEAT PUMP] INSTALLED PER SANS 10106 / SANS 1307). ALL EXPOSED HOT WATER PIPING TO BE INSULATED TO REQUIRED R-VALUE.
- ROOF & CEILING INSULATION: INSTALL NON-COMBUSTIBLE BULK THERMAL INSULATION (e.g. GLASSWOOL / POLYESTER / MINERAL WOOL) ABOVE CEILING TO ACHIEVE A MINIMUM TOTAL ROOF ASSEMBLY R-VALUE OF [INSERT R-VALUE FOR YOUR ZONE, e.g. R3.70 m²·K/W] IN ACCORDANCE WITH SANS 10400-XA.
- FENESTRATION & GLAZING PERFORMANCE: TOTAL NET FLOOR AREA = [X] m²; TOTAL GLAZED AREA = [X] m² ([X]% OF NET FLOOR AREA). [EITHER: GLAZING AREA <= 15% OF NET FLOOR AREA, THUS DEEMED-TO-SATISFY WITHOUT RATIONAL FENESTRATION CALCULATION] OR [GLAZING EXCEEDS 15%: ATTACHED FENESTRATION PERFORMANCE CALCULATION / SANS 204 RATIONAL DESIGN BY COMPETENT PERSON CERTIFYING SHGC AND U-VALUE COMPLIANCE USING (SPECIFY GLASS, e.g. 6.38mm LOW-E LAMINATED) IN (ALUMINIUM / THERMALLY BROKEN) FRAMES].AutoCAD vs. Revit vs. ArchiCAD: How to Standardise Your Note Library
Maintaining consistent SANS 10400 notes across a multi-person practice prevents junior draughtspersons from copying outdated specifications from old project files. Below is the recommended BIM and CAD setup used by high-throughput South African architectural studios.
| Software Platform | Recommended Storage Method | Best Practice for Updates | Pre-Submission Audit Tip |
|---|---|---|---|
| AutoCAD / AutoCAD LT | Dedicated SANS_Notes.dwg source file inserted via Tool Palettes or attached as an XREF on Title/Note sheets. | Separate generic statutory notes (XREF) from project-specific schedule notes (editable MTEXT blocks). | Run a visual check on viewport scales and ensure ANNOALLVISIBLE does not hide annotative leader notes on PDF export. |
| Autodesk Revit | Central Legend Views for standard SANS 10400 blocks + Keynote Schedules linked to wall/window families. | Lock Legend Views in your firm's .rte project template so notes appear identically across sheets without duplicating text. | Ensure Keynote values match your Window/Door Schedule parameters (e.g. glazing thickness and safety rating under Part N). |
| Graphisoft ArchiCAD | Dedicated Worksheets placed as Drawings onto Master Layouts or Note Sheets. | Update Master Worksheet once per SANS edition change; use Autotext fields for Erf Number, Zoning, and Project Author. | Verify translator pen sets so fine text (1.8mm–2.5mm plotted height) remains crisp on council A1/A0 PDF submissions. |
Top 10 Municipal Omission Traps (Why Council Refers Plans Back)
Even experienced practices stumble on recurring omissions when rushing to meet client deadlines. Our pre-submission audit logs show the following ten traps account for the majority of administrative referrals across Johannesburg, Cape Town, Tshwane, and eThekwini:
| Omission Trap | SANS 10400 Part | Municipal Impact (CoJ / CoCT / Tshwane / eThekwini) | Exact Drawing Fix |
|---|---|---|---|
| 1. Unspecified Safety Glazing Locations | Part N | Examiner refuses to clear elevations/schedules because low-level windows or shower screens lack SANS 1263-1 callouts. | Add an explicit "Safety Glazing (SG)" column to your Window & Door Schedule and tag low-level panes (<500mm above FFL) directly on elevations. |
| 2. Missing Part XA Climatic Zone & R-Value | Part XA | Immediate Energy Efficiency hold; CoCT and CoJ strictly verify Roof R-value and 50% alternative hot water source. | State the exact Climatic Zone, total roof R-value, solar/heat pump spec, and net floor vs. glazing percentage on Sheet 01. |
| 3. Stormwater Connected or Unclear on Site Plan | Part P & Bylaws | Referral by Engineering Services / Stormwater Department if roof downpipes or courtyard gullies lack discharge routing. | Show directional arrows from every downpipe to street kerb, swale, or engineered soakaway, plus the mandatory "No Stormwater in Sewer" note. |
| 4. Unannotated Retaining Walls > 1.2m | Part A & Part K | Automatic trigger for Form 1 & Form 2 structural engineer appointment; plan held until engineer details or appointment uploaded. | Dimension all retaining wall heights on sections and add a leader note: "Structural Engineer Form 1/2 Appointment Required". |
| 5. Missing Gully Rim & SVP Termination Heights | Part P | Health/Building Inspector rejects drainage layout for potential backflow or odour ingress near habitable windows. | Annotate gully rim (+150mm above paving) and Soil Vent Pipe (+900mm above windows within 2.5m) on drainage plan and sections. |
| 6. No DPC Continuity Shown on Wall Sections | Part K | Plan returned for construction detail deficiency, especially on stepped sloping sites or plastered boundary walls. | Draw heavy dashed DPC lines at +150mm above FGL and under all window sills, paired with the 375-micron SANS 952 Type B note. |
| 7. Garage-to-House Door Lacks Fire Rating Note | Part T | Fire Department or BCO refuses plan due to missing 30-min fire separation and self-closer callout. | Label connecting door on plan and door schedule as "FD30 / 40mm Solid-Core Timber Fire Door with Self-Closer, No Air Grille". |
| 8. Balustrade Height & 100mm Sphere Omission | Part D | Plan referred back whenever balconies, raised stoops (>1000mm drop), or staircases lack child-safety notes. | Tag all balustrades on elevations and sections: "1000mm Min. Height Balustrade, Max. 100mm Openings (SANS 10400-D)". |
| 9. Internal WCs Without Ducted Mechanical Vent | Part O | Rejected under Public Health / Building Control check if exhaust fan is shown venting into ceiling cavity or unannotated. | Draw dotted duct route from internal WC/en-suite to external wall/roof cowl and cite SANS 10400-O extraction rate. |
| 10. Outdated SABS 0400 References | Part A | Signals poor quality control to examiners and invites deeper scrutiny across every discipline on the sheet set. | Audit your CAD/BIM templates quarterly to purge "SABS 0400" and replace with current SANS 10400 parts and municipal bylaws. |
Streamline Your Pre-Submission Compliance Audit
Copying standard notes into your AutoCAD or Revit template is the essential first layer of protection—but real-world rejections happen when a note contradicts a line on your section, or when a window schedule drops a safety-glazing code during a late client revision. Plan Comply's Pre-Submission Audit Engineering workflow helps South African architects, technologists, and draughtspersons catch missing SANS 10400 annotations, Part XA mismatches, and municipal checklist gaps before your drawings ever hit the council counter. Explore our studio and solo practitioner plans or run a pre-lodgement check directly in our Plan Comply submission audit workspace.
Frequently Asked Questions: SANS 10400 Drawing Notes
1. Can I use the exact same SANS 10400 notes for Johannesburg, Cape Town, Tshwane, and eThekwini?
The core technical wording derived from SANS 10400 Parts A through XA applies nationwide because Act 103 of 1977 is national legislation. However, your title block, zoning parameters, stormwater attenuation clauses, and Climatic Zone R-values (Part XA) must be adapted for each municipality's specific Land Use Scheme / Development Management Scheme and local bylaws. For example, Cape Town and Johannesburg have distinct heritage, stormwater, and digital submission naming conventions.
2. Do I need a Form 1 and Form 2 Competent Person note on a standard single-storey house plan?
Even on a standard single-storey house (Occupancy H4), engineered elements frequently fall outside the deemed-to-satisfy empirical rules of SANS 10400—most commonly prefabricated timber roof trusses (A19 rational design), reinforced concrete slabs on poor soils, swimming pools, or boundary retaining walls exceeding 1.2m. Including a clear Form 1 / Form 2 declaration note ensures the BCO knows which elements are covered by an ECSA-registered structural engineer.
3. What is the difference between SANS 10400-XA Edition 1 and SANS 10400-XA:2021 in drawing notes?
SANS 10400-XA:2021 updated South Africa's climatic zone map (expanding from 6 to 7 climatic zones), revised minimum roof and wall R-values, and tightened fenestration/glazing calculation rules. Always state on your drawing which edition and Climatic Zone your design complies with, and verify whether your local municipality enforces the 2021 edition for new submissions.
4. Where should SANS 10400 standard notes be placed in an AutoCAD or Revit drawing set?
Municipal examiners prefer General Statutory Notes, Title-Block Declarations, and Part XA summaries on Sheet 01 (Site Plan / General Notes Sheet), while element-specific notes—such as DPC details (Part K), balustrade heights (Part D), and ceiling clearances (Part C)—should also be called out directly via leaders on sections and elevations. Glazing and fire-door notes belong both in your General Notes and inside your Window and Door Schedules.
5. Is it legally permitted to copy SABS SANS 10400 wording verbatim onto commercial building plans?
No—verbatim reproduction of large sections of SABS standards without a licence infringes SABS copyright. Instead, architectural professionals should use synthesized, original compliance specification notes (like the CAD/BIM blocks above) that reference the relevant SANS 10400 part, state the specific project performance parameters (such as R-values, gradients, or safety glass marks), and direct the contractor to comply with the official standard purchased from SABS.
Ready to Eliminate Municipal Plan Rejections?
Audit your AutoCAD, Revit, or ArchiCAD PDF drawing set against SANS 10400 Parts A–XA and South African municipal checklists before you submit.
Run a Pre-Submission Audit NowAudit Your Plans Before Municipal Submission
Run your architectural drawings through Plan Comply automated compliance scanner.
Launch Pre-Submission Audit